Vacuum Switches  
 
 
Loss of Vacuum and High Vacuum switches, for use with Chlorine gas under vacuum. For monitoring of the systems vacuum condition.
LOSS OF VACUUM SWITCH
BM5964, Loss of Vacuum: switch is designed to provide one normally open and one Normally closed alarm contact in the presence of a loss of vacuum. It should be mounted Vertically as close to the Ejector as practical and -after the gas rate valve. The alarm point is adjustable between 28 and 29 Inches of Mercury to allow the switch to actuate at the Required vacuum.
Contacts rated at : 5 A @ 250 Vac or 28 Vdc maximum, (Resistive Load),
Enclosure : NEMA 4X.
Dimensions : 102 mm W x 94 mm D x 145 mm H.
Weight : 2 kg.
HIGH VACUUM SWITCH
BM5987, High Vacuum switch is designed to provide one normally open and one normally closed alarm contact in the presence of a high vacuum level. It should be mounted Vertically as close to the Vacuum Regulator as practical and before the gas rate valve. The alarm point is adjustable between 2 and s: Inches of Mercury to allow the switch to actuate at the required vacuum.
Contacts rated at : 5 A @ 250 Vac or 28 Vdc maximum, (Resistive Load)
Enclosure : NEMA 4X.
Dimensions : 102 mm W x 94 mm 0 x 145 mm H.
Weight : 2 kg.


  Top
 
lTEM QTY    DESCRIPTION   PART NO.
1 1   ADJUSTMENT PLUG   U-2128
2 1   O-RING   OV- 1 1-115
3 1   HOUSING BCDY   U -2129
4 1   SPRING   SEE CHART
5 2   SCREW, 6-32 X 3/8 LG BD HD   N-144
6 1   SPRING ADAPTOR   U-2119
7 1   LOWER DIAPHRAGM PIN   T-1409
8 2   DIAPHRAGM   D-102
9 1   DIAPHRAGM SPACER   U-2120
10 1   UPPER DIAPHRAGM PIN   T-1402
11 1   DIAPHRAGM SEAL   U-137-1
12 1   ENCLOSURE   U-2133
13 2   SCREW, 10-24 X 3/8 LG RD HD   N- 122
14 2   SCREW, 2 -56 X 1/2 LG RD HD   N-137
15 1   MICROSWITCH   R-5615
16 1   LEVER ASSEMBLY   A-243
17 2   NUT, 10-24   N-173
18 2   SCREW, 10- 24 X 1/2 LG RD HD   N-282
19 1   MOUNTING BRACKET   T-1242
20 1   TUBING CONNECTOR, 1/4 X 3/8 X 90'   F-119-1
21 1   SCREW, 2-56 X 3/16 LG RD HD   11802

ITEM PART NUMBER
LOW VACUUM HIGH VACUUM
4 R-5589 R-5588
NOTES:
1. (+) INDICATES RECOMMENDED AS MINIMUM SPARE PARTS, QUANTIT RECOMMENDATIONS ARE FOR AVERAGE USE AND CONDITIONS. ADDITIONAL PARTS AND OUANTITIES SHOULD BE CONSIDERED WHERE THE EOUIPMENT IS USED TO ITS FULLEST CAPABILITY OF WHERE LOCATED IN AN AREA REMOTE FROM CONVENIENT SERVICE.
2.
TO RETROFIT A SWITCH ORDER:
  LOW TO HIGH.....BM- 5988
  HIGH TO LOW…..BM- 5989
3.
TO ORDER COMPLETE ASSEMBLY
  LOW VACUUM…..BM-5964
  HIGH VACUUM….BM-5987