Leak Detector  
 
 
Technical Data Sheet
Gas to be detected : Chlorine gas
Range / Resolution : 0 to 20 PPM
Accuracy : ±1% of the full scale value.
Sensor type :
Long life Electrochemical sensor, Imported make
Sensor life :
Expected 2 year for Electrochemical sensor.
Set point :
Two independent set point, LO & HI with blinking indication with programmable latch/non-latch facility only for indication purpose. (There is no relay output)
Display : Easy- to-read 0.5”, 3.5 digit LCD Display
Setting : Setting by 4 keys on front panel i.e. ‘SET / NEXT’, ‘UP’, ‘DOWN’ & ‘TEST / BACK’ keys.
Loop output : 4-20mA, with permissible load 750 ohm at 24Vdc, 25mA.
Monitoring : i) By display : Shows “Err” indication. Sensor Open/Over Indication
ii) By loop current : Selectable, upscale current : 22mA, Down scale current : 3.6mA to 3.8mA.
Supply Voltage : 14VDC to 36VDC, normally 24 VDC, 25mA
Digital filter : Select damping factor 1 to 99 to smooth input signal.
Operating ambient Temperature : 0 to 50 degree C ± 5%
Relative humidity : Below 95%, non condensing.
Sensor Housing : P.V.C.
Enclosure Detail : FLAMEPROOF , Cast Alluminium alloy, LM-6 / C.I Enclosure, IP-65, As per IS : 2148 – 1981, 145mm (Dia) X 130mm (Height) X 85mm (D) Mounting : Wall Mounting / Stand Mounting, 250 Grams
Model : TOX-107-FLP
 
 